XR64CX
XR Series • Refrigeration Controller
Quick Info
Output Functions
Two-stage compressor controller for large capacity systems
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 3 |
| Buttons | 4 |
| LED Indicators | Stage1, Stage2, Defrost, Fan, Alarm |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 100-240V AC |
| Frequency | 50/60Hz |
| Power Consumption | 5VA |
Sensor Inputs
| Probe Inputs | 2 |
| Probe Type | NTC 10K |
| Temp Range | -50 to 110°C |
| Accuracy | ±0.5°C |
Relay Outputs
| Relay Outputs | 5 |
| Relay Rating | 8A/250VAC |
Physical
| Panel Size | 32x74 mm |
| Depth | 65 mm |
| IP Rating | IP65 (front) |
| Weight | 110 g |
Operating Conditions
| Operating Temp | -5 to 55°C |
| Storage Temp | -25 to 70°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| Pb1 | Air Probe | Input |
red/white
|
| Pb2 | Evap Probe | Input |
red/white
|
| R1 | Compressor Stage 1 | Output |
black
|
| R2 | Compressor Stage 2 | Output |
black
|
| R3 | Defrost Heater | Output |
black
|
| R4 | Fan | Output |
black
|
| R5 | Alarm | Output |
red
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| Set | Setpoint | -50 to 110 | -20 °C | Temperature setpoint |
| HY | Differential | 0.1 to 25.5 | 2 °C | Switching differential |
| HY2 | Stage 2 Differential | 0.1 to 25.5 | 4 °C | Stage 2 start offset |
| dEL | Stage Delay | 0 to 30 | 5 min | Delay between stages |
| tdF | Defrost Type | 0-3 | 1 | 0=Off, 1=Electric, 2=Gas, 3=Off-cycle |
| dIt | Defrost Interval | 0 to 24 | 6 h | Hours between defrosts |
| dEt | Defrost Duration | 1 to 120 | 45 min | Max defrost time |
| dSt | Defrost Stop | -50 to 50 | 10 °C | End defrost temperature |
Error Codes
Solution: Check air probe
Solution: Check evaporator probe
Solution: Check both compressor stages
Solution: Check staging parameters
Solution: Check heater element
Frequently Asked Questions
When temperature exceeds Set+HY2 after dEL delay
Yes, configure stage 2 for unloader valve
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Dixell
Country: Italy
Parent: Emerson Climate Technologies