Dixell

XR60CX

XR Series • Refrigeration Controller

XR60CX

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 2
Relay Outputs 3
Communication RS485 (optional)
Panel Size 32x74 mm

Output Functions

R1 Compressor
R2 Defrost
R3 Fan

Advanced refrigeration controller with defrost and fan management

Technical Specifications

Display & Interface

Display Type LED
Display Digits 3
Buttons 4
LED Indicators Compressor, Defrost, Fan, Alarm

Power Supply

Voltage 230V AC
Voltage Range 110-230V AC
Frequency 50/60Hz
Power Consumption 4VA

Sensor Inputs

Probe Inputs 2
Probe Type NTC
Temp Range -50 to 110°C
Accuracy ±0.5°C

Relay Outputs

Relay Outputs 3
Relay Rating 8A/250VAC

Physical

Panel Size 32x74 mm
Depth 59 mm
IP Rating IP65 (front)
Weight 100 g

Operating Conditions

Operating Temp 0 to 55°C
Storage Temp -25 to 60°C

Wiring Terminals

Terminal Function Type Wire Color
1 Power L Input
brown
2 Power N Input
blue
3 Probe 1 (+) Input
red
4 Probe 1 (-) Input
white
5 Probe 2 (+) Input
red
6 Probe 2 (-) Input
white
7 Digital Input Input
gray
8 DI Common Input
gray
9 Relay 1 NO (Comp) Output
black
10 Relay 1 COM Output
black
11 Relay 2 NO (Def) Output
orange
12 Relay 2 COM Output
orange
13 Relay 3 NO (Fan) Output
green
14 Relay 3 COM Output
green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SEt Setpoint -50 to 110 0 °C Temperature setpoint
Hy Differential 0.1 to 25.5 2 °C Switching differential
LS Low Limit -50 to SET -50 °C Minimum setpoint
US High Limit SET to 110 50 °C Maximum setpoint
CA Calibration Pb1 -12 to 12 0 °C Room probe offset
C2 Calibration Pb2 -12 to 12 0 °C Evap probe offset
Cd Comp Delay 0 to 15 0 min Startup delay
Ct Min Off Time 0 to 15 3 min Minimum compressor off
dt Defrost Type 0=Off, 1=Elec, 2=Gas 1 Defrost method
dI Defrost Interval 0 to 24 8 hr Time between defrosts
dP Defrost Duration 0 to 99 30 min Maximum defrost time
dE Defrost End Temp 0 to 50 8 °C Termination temperature
dd Drip Time 0 to 15 2 min Drain time after defrost
Fd Fan Delay 0 to 15 0 min Fan restart delay
Fc Fan Cutout 0=Off, 1=On 1 Stop fan during defrost
AL Low Alarm -50 to SET -10 °C Low temp alarm
AH High Alarm SET to 110 15 °C High temp alarm
Ad Alarm Delay 0 to 255 60 min Alarm delay time

Error Codes

E1 Room probe fault

Solution: Check probe 1 wiring

E2 Evaporator probe fault

Solution: Check probe 2 wiring

HI High temperature alarm

Solution: Check refrigeration system

LO Low temperature alarm

Solution: Check setpoint and defrost

dF Defrost in progress

Solution: Normal operation

dr Door open

Solution: Close door