XR30CX
XR Series • Refrigeration Controller
Quick Info
Output Functions
Two-probe controller with off-cycle defrost and alarm relay
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 3 |
| Buttons | 4 |
| LED Indicators | Compressor, Defrost, Alarm |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 110-230V AC |
| Frequency | 50/60Hz |
| Power Consumption | 3VA |
Sensor Inputs
| Probe Inputs | 2 |
| Probe Type | NTC |
| Temp Range | -50 to 110°C |
| Accuracy | ±0.5°C |
Relay Outputs
| Relay Outputs | 2 |
| Relay Rating | 8A/250VAC |
Physical
| Panel Size | 32x74 mm |
| Depth | 59 mm |
| IP Rating | IP65 (front) |
| Weight | 90 g |
Operating Conditions
| Operating Temp | 0 to 55°C |
| Storage Temp | -25 to 60°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| 1 | Power L | Input |
brown
|
| 2 | Power N | Input |
blue
|
| 3 | Probe 1 (+) | Input |
red
|
| 4 | Probe 1 (-) | Input |
white
|
| 5 | Probe 2 (+) | Input |
red
|
| 6 | Probe 2 (-) | Input |
white
|
| 7 | Relay 1 NO (Comp) | Output |
black
|
| 8 | Relay 1 COM | Output |
black
|
| 9 | Relay 2 NO (Alarm) | Output |
red
|
| 10 | Relay 2 COM | Output |
red
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SEt | Setpoint | -50 to 110 | 4 °C | Temperature setpoint |
| Hy | Differential | 0.1 to 25.5 | 2 °C | Switching differential |
| CA | Room Calibration | -12 to 12 | 0 °C | Room probe offset |
| C2 | Evap Calibration | -12 to 12 | 0 °C | Evaporator probe offset |
| dI | Defrost Interval | 0 to 24 | 8 hr | Time between defrosts |
| dP | Defrost Duration | 0 to 60 | 20 min | Off-cycle defrost time |
| dE | Defrost End Temp | 0 to 50 | 8 °C | Termination temperature |
| AL | Low Alarm | -50 to SET | -5 °C | Low temp alarm |
| AH | High Alarm | SET to 110 | 15 °C | High temp alarm |
Error Codes
Solution: Check probe 1 wiring
Solution: Check probe 2 wiring
Solution: Check system
Solution: Check setpoint
Frequently Asked Questions
Activates on high/low temperature or probe fault, can trigger buzzer or remote alarm
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Dixell
Country: Italy
Parent: Emerson Climate Technologies