Dixell

XC660D

XC Series • Refrigeration Controller

XC660D

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 4
Relay Outputs 6
Communication RS485 Modbus
Panel Size 71x29 mm

Output Functions

R1 Compressor 1
R2 Compressor 2
R3 Compressor 3
R4 Defrost
R5 Fan
R6 Alarm

Pack controller for parallel compressor systems

Technical Specifications

Display & Interface

Display Type LED
Display Digits 4
Buttons 6
LED Indicators Comp 1, Comp 2, Comp 3, Defrost, Fan, Alarm

Power Supply

Voltage 230V AC
Voltage Range 100-240V AC
Frequency 50/60Hz
Power Consumption 8VA

Sensor Inputs

Probe Inputs 4
Probe Type NTC / PT1000
Temp Range -50 to 150°C
Accuracy ±0.3°C

Relay Outputs

Relay Outputs 6
Relay Rating 8A/250VAC

Physical

Panel Size 71x29 mm
Depth 75 mm
IP Rating IP65 (front)
Weight 180 g

Operating Conditions

Operating Temp -10 to 55°C
Storage Temp -30 to 70°C

Wiring Terminals

Terminal Function Type Wire Color
L Power L Input
brown
N Power N Input
blue
Pb1 Probe 1 (Room) Input
red/white
Pb2 Probe 2 (Evap) Input
red/white
Pb3 Probe 3 (Disch) Input
red/white
Pb4 Probe 4 (Aux) Input
red/white
DI1 Digital Input 1 Input
gray
DI2 Digital Input 2 Input
gray
R1 Relay 1 (Comp 1) Output
black
R2 Relay 2 (Comp 2) Output
black
R3 Relay 3 (Comp 3) Output
black
R4 Relay 4 (Defrost) Output
orange
R5 Relay 5 (Fan) Output
green
R6 Relay 6 (Alarm) Output
red
A RS485 A Comm
blue
B RS485 B Comm
yellow

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SEt Setpoint -50 to 150 0 °C Main setpoint
Hy Differential 0.1 to 25.5 2 °C Stage 1 differential
Hy2 Stage 2 Diff 0.1 to 25.5 4 °C Stage 2 differential
Hy3 Stage 3 Diff 0.1 to 25.5 6 °C Stage 3 differential
CdL Stage Delay 0 to 255 5 min Delay between stages
nC Num Compressors 1 to 3 2 Number of stages
Rot Rotation 0=No, 1=Yes 1 Compressor rotation
dt Defrost Type 0-4 1 Defrost method
dI Defrost Interval 0 to 48 8 hr Time between defrosts
dP Defrost Duration 0 to 255 30 min Max defrost time

Error Codes

E1 Probe 1 fault

Solution: Check room probe

E2 Probe 2 fault

Solution: Check evaporator probe

E3 Probe 3 fault

Solution: Check discharge probe

E4 Probe 4 fault

Solution: Check auxiliary probe

HI High temp alarm

Solution: Check system capacity

LO Low temp alarm

Solution: Check setpoint/defrost

HP High pressure

Solution: Check condenser

LP Low pressure

Solution: Check refrigerant charge

Frequently Asked Questions

Alternative Models (Cross Reference)

Eliwell EWDR 984 Carel pCO5 Danfoss AKC 115

Manufacturer Information

Brand: Dixell

Country: Italy

Parent: Emerson Climate Technologies

Visit Manufacturer Website