XC440C
XC Series • Refrigeration Controller
Quick Info
Output Functions
Condensing unit controller with discharge pressure control
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 4 |
| Buttons | 5 |
| LED Indicators | Compressor, Fan Low, Fan High, Alarm |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 100-240V AC |
| Frequency | 50/60Hz |
| Power Consumption | 5VA |
Sensor Inputs
| Probe Inputs | 3 |
| Probe Type | NTC 10K / 4-20mA |
| Temp Range | -50 to 150°C |
| Accuracy | ±0.3°C |
Relay Outputs
| Relay Outputs | 4 |
| Relay Rating | 8A/250VAC |
Physical
| Panel Size | 71x29 mm |
| Depth | 65 mm |
| IP Rating | IP65 (front) |
| Weight | 110 g |
Operating Conditions
| Operating Temp | -10 to 55°C |
| Storage Temp | -25 to 70°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| Pb1 | Suction Pressure | Input |
4-20mA
|
| Pb2 | Discharge Pressure | Input |
4-20mA
|
| Pb3 | Ambient/Liquid Temp | Input |
NTC
|
| DI1 | HP Switch | Input |
gray
|
| R1 | Compressor | Output |
black
|
| R2 | Fan Low Speed | Output |
black
|
| R3 | Fan High Speed | Output |
black
|
| R4 | Alarm | Output |
red
|
| AO | 0-10V Fan Speed | Output |
green
|
| A/B | RS485 | Comm |
yellow/green
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SSP | Suction Setpoint | -1.0 to 15 | 4.5 bar | Suction pressure SP |
| DSP | Discharge Setpoint | 5 to 35 | 18 bar | Discharge pressure SP |
| dFS | Fan Step Diff | 0.5 to 5 | 2 bar | Fan staging band |
| HPA | HP Alarm | DSP to 45 | 28 bar | High pressure alarm |
| LPA | LP Alarm | -1.0 to SSP | 1.0 bar | Low pressure alarm |
| FCt | Fan Control | 0-2 | 1 | 0=Off, 1=Stepped, 2=VFD 0-10V |
| Add | Modbus Address | 1 to 247 | 1 | RS485 address |
Error Codes
Solution: Check condenser, fan
Solution: Check charge, leaks
Solution: Check 4-20mA signal
Solution: Check 4-20mA signal
Frequently Asked Questions
Yes, use 0-10V output with FCt=2
Yes, adjusts DSP based on ambient temp
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Dixell
Country: Italy
Parent: Emerson Climate Technologies