Side-by-side refrigerant comparison with pressure-temperature data

Properties Comparison

Property R-22 R-32
TypePurePure
GWP 1810 675

Pressure-Temperature Comparison (PSIG)

Temp (°F) R-22 (psig) R-32 (psig) Difference
-40°F -3.8 10.3 -14.1
40°F 65.9 130.5 -64.6
50°F 79.1 152.8 -73.7
60°F 93.6 177.3 -83.7
130°F 272.8 468.9 -196.1
140°F 304.6 519.5 -214.9
150°F 338.9 573.9 -235.0

Frequently Asked Questions

What is the difference between R-22 and R-32?

R-22 has a GWP of 1810 and is a pure refrigerant, while R-32 has a GWP of 675 and is a pure refrigerant. They have different operating pressures, capacity characteristics, and application ranges.

Can I replace R-22 with R-32?

Direct replacement between R-22 and R-32 is not recommended without thorough system evaluation. Check compressor compatibility, oil type, pressure ratings, and safety classification before any refrigerant change.

Which has lower GWP, R-22 or R-32?

R-32 has a lower GWP (675) compared to R-22 (1810).